Remote surveillance is often installed where regular human presence is difficult, expensive or simply unnecessary. Construction sites, critical infrastructure, remote perimeters and forestry applications may need cameras, thermal imaging, communication and local processing to remain active around the clock.
The electrical demand of individual surveillance devices is usually moderate and often well defined through PoE standards. Many modern cameras and related devices use Power over Ethernet, combining data and electrical power through the same cable. The challenge starts when this power has to be supplied continuously for days or weeks without a grid connection
The more difficult question is what happens when that equipment has to remain operational for several days without grid connection. A camera node drawing only a few tens of watts may appear to be a small electrical load. But once it has to operate continuously for days or weeks, the energy requirement becomes significant.
The question therefore changes from:
How much power does the equipment need?
to:
How much energy must be available to keep the surveillance mission running until the next planned intervention?
PoE gives a useful reference for system sizing
PoE standards provide a practical way of understanding the power level of many surveillance installations.
| PoE standard | Common name | Type | PSE output | Power available at device |
|---|---|---|---|---|
| IEEE 802.3af | PoE | Type 1 | 15.4 W | 13 W |
| IEEE 802.3at | PoE+ | Type 2 | 30 W | 25.5 W |
| IEEE 802.3bt | PoE++ / 4PPoE | Type 3 | 60 W | 51 W |
| IEEE 802.3bt | PoE++ / 4PPoE | Type 4 | 90 W | 71.3 W |
For a simple fixed camera, Type 1 or Type 2 may be sufficient. More demanding devices such as PTZ cameras, thermal imaging, integrated illumination or edge-processing equipment can move into the higher PoE classes.
But the PoE rating is not necessarily the continuous power consumption of the device.
A PoE++ camera may be capable of drawing 60 W during demanding conditions while consuming considerably less during normal operation. Heaters, IR illumination, PTZ movement and local processing can create temporary peaks.
That distinction matters when designing the energy system.
The power source must be able to support the equipment, but it does not necessarily have to continuously generate the maximum value defined by the PoE class.
Size the continuous power around the mission
This is where a hybrid architecture becomes useful. The fuel cell can be sized around the continuous or average energy requirement, while a battery supports temporary peaks.
The architecture can therefore look like:
A surveillance node may, for example, contain a camera capable of operating within a 60 W PoE Type 3 envelope. That does not automatically mean the fuel cell has to supply 60 W continuously.
If the normal system demand is closer to 35–40 W and the higher load occurs only when IR illumination, heating or movement is active, the battery can provide the temporary difference.
The fuel cell then concentrates on what matters for a long-duration installation: continuously replacing the energy being consumed over the course of the mission.
Power and mission duration remain separate
PoE helps define the electrical side of the system and the mission duration defines the energy side.
A 40 W continuous load requires approximately:
- 0.96 kWh per day
- 6.7 kWh per week
- 13.4 kWh for two weeks
At 80 W, those values double. This is why even modest PoE-powered equipment can create a substantial energy requirement when it operates continuously.
Keeping power and energy separate makes the system easier to configure.
More fuel-cell capacity → supports more continuous electrical load
More hydrogen storage → extends operating time
A lower-power surveillance node that needs to operate for a week may therefore use the same fuel-cell configuration as a shorter mission, but with additional hydrogen storage.
Longer autonomy can reduce site visits
For remote equipment, energy quickly becomes a maintenance and logistics issue. Every time the system requires recharging or energy replacement, somebody may need to travel to the site. Depending on the location, that can involve personnel, vehicles, access arrangements and significant travel time.
Increasing the available mission energy extends the interval between those interventions.
FCT’s current preliminary estimations illustrate the relationship:
| Fuel-cell output | Hydrogen storage | Pressure | Estimated operating time* |
|---|---|---|---|
| 45 W | 3 L | 350 bar | 29.4 h |
| 45 W | 5 L | 350 bar | 49.0 h |
| 45 W | 9 L | 350 bar | 88.3 h |
| 45 W | 20 L | 350 bar | 196.1 h |
| 90 W | 3 L | 350 bar | 14.7 h |
| 90 W | 5 L | 350 bar | 24.5 h |
| 90 W | 9 L | 350 bar | 44.1 h |
| 90 W | 20 L | 350 bar | 98.1 h |
* Preliminary FCT engineering estimates at rated fuel-cell output. Actual runtime depends on the final system configuration, PoE conversion losses, operating conditions and application load.
The 45 W system, for example, can move from approximately 29 hours to more than eight days of continuous fuel-cell operation simply by changing the hydrogen storage.
The 200 W-class configuration with a 5 L hydrogen cylinder, for example, provides approximately 2.2 kWh of additional usable electrical energy.
How much extra robot runtime that creates depends on terrain, speed, payload, average power demand and the added system weight. The important point is that the range extender continuously replaces part of the energy that would otherwise come from the battery.
The right question is therefore a little more complex then: How long can a fuel cell extend my missions range.
It is: How can I find the best possible balance between Battery Weight & Size, Fuel Cell Power and Hydrogen Storage size to optimize range, weight & cost.
Keep the logistics simple at the surveillance site
A surveillance node does not necessarily need a complex hydrogen infrastructure. For early deployments, the simplest solution is often a pre-filled exchange cylinder.
During a service visit, the cylinder is replaced, the system is checked and the depleted cylinder returns to the supply chain.
As the deployment grows, the logistics can grow with it. A few installations may use supplier-filled cylinders. Several systems in one region can be supported from a central cylinder stock. Larger deployments may justify central hydrogen storage and local refilling.
The important point is that the individual surveillance node remains largely unchanged. The power architecture can stay the same while both mission duration and hydrogen logistics scale independently.
Start with the surveillance equipment
For an initial assessment, the PoE configuration gives us a useful starting point:
- Which devices are installed?
- Which PoE classes do they require?
- What is their normal consumption, and which functions create temporary peaks?
From there, the mission questions follow.
- How long should the installation remain operational?
- How difficult is the site to reach?
- How often should somebody realistically have to return?
Those answers define the combination of continuous fuel-cell power, battery buffering and hydrogen storage.
The principle is straightforward:
- PoE defines the equipment power envelope.
- The average load defines the continuous power requirement.
- The mission duration defines the stored energy requirement.
FCT’s Lamina-based architecture brings these elements together around the surveillance mission rather than forcing the application around a predefined power system.